Load duration curve
A time chart shows when a power occurred. The load duration curve shows how long a certain power was needed. Exactly that decides on grid connection, demand charge, storage size and peak load management.
- One click: from the time chart to the load duration curve
- Peak load, average load and base load as figures
- Period freely selectable — month, quarter, heating season
The load duration curve sorts all power values of a period by size: the highest power on the left, the lowest on the right. The horizontal axis shows the number of hours. This way you read off how many hours a year a certain power was needed at least — and how small the share of the peaks actually is.
Load duration curve at a glance
What the load duration curve looks like in eco2lot
The same data set, three views: the whole curve with figures, the steep start with the peaks and the flat end with the base load.
Horizontally the duration in percent of the period, vertically the power. Bottom right the figures: peak load 341 kW, average load 123 kW — the peak sits almost three times above the average.
From 340 kW the curve drops to around 200 kW within the first percent. These peaks determine the demand charge — and are the first lever.
Over wide stretches the power sits around 100 kW — at night and at the weekend too. Whoever saves 10 kW here saves them around the clock.
What is inside Load duration curve
What is a load duration curve?
Take all quarter-hour values of the electrical power of one year — 35,040 values. Sort them from large to small. The resulting curve is the load duration curve.
- Left: the highest power of the year — the load peak
- Right: the power that is always present — the base load
- In between: how many hours which power was needed
Your benefitOne curve answers the question a time chart keeps quiet: how often does this actually happen?
What you recognize from it
- Load peaks: how high are they — and in how few hours do they occur?
- Base load: which power runs around the clock — at night and at the weekend too?
- Power demand: which power covers 95 percent of all hours?
- Grid connection: is the ordered connection capacity fitting, too large or too tight?
Your benefitThe gut feeling "we have peaks" becomes a reliable number.
What you use it for
- Plan peak load management: which power is worth capping?
- Size battery storage: how much energy sits in the peak hours?
- Assess own generation: which power could PV or CHP cover permanently?
- Reduce the demand charge: the grid operator bills the highest quarter hour
Your benefitInvestments in storage, generation and control are calculated with real hours instead of assumptions.
Load duration curve in eco2lot
- For every meter, every plant, every site — or the whole works
- Period freely selectable: month, quarter, year, heating season
- Overlay several years or sites
- Right next to live chart and heatmap in the dashboard
Your benefitThe curve stands live in the dashboard — free of Excel export and sorting by hand.
Step by step: how the curve is built
Four steps from the time series to the load duration curve — eco2lot performs them automatically.
1 · Measure
The meter delivers the average power in kilowatts every 15 minutes — exactly as with the grid operator.
2 · Sort
All values of the period are ordered from the highest to the lowest power. The time reference plays no further role.
3 · Plot
Horizontally the number of hours, vertically the power. Every point says: this power was needed for at least this many hours.
4 · Read off
A steep start means short, high peaks. A long flat end means a high base load. Both are concrete levers.
The load duration curve shows how long a power was needed — the time chart shows when
The time chart answers "When was the peak?". The load duration curve answers "How many hours a year do I really need this power?". For grid connection, storage and peak load management, the second question is the decisive one.
- Readings
- Sort
- Read off hours
- Assess the peak
- Action
Afterwards you can …
-
Quantify and prioritize load peaks with hours per year.
-
Size storage, PV or CHP with real load data.
-
Negotiate the ordered connection capacity with the grid operator on facts.
What you should know about Load duration curve
What is the difference between load duration curve and load profile?
The load profile is the time series of the power — quarter hour by quarter hour in chronological order. The load duration curve is the same data set sorted by size. The load profile shows when, the load duration curve how long.
How do I read off whether battery storage pays off?
Look at the steep start of the curve. The area between the desired peak and the curve corresponds to the energy the storage has to deliver. If this area is narrow and high, a small storage is enough for a big effect.
Which data does eco2lot need for it?
Power values at regular intervals — typically 15-minute values of the main meter or second to minute values from your own measuring points. eco2lot reads both directly.
Is the load duration curve available for heat or gas as well?
Yes. The principle works for every power: electrical, thermal, gas or compressed air. For the heating season it shows how many hours the full boiler output is really needed.